In protective earthing, all of the conductive parts not belonging to the service circuit are connected with the protective earthing device by means of the protective conductor. Since the fault current is conducted through the earthing resistance, no impermissibly high contact voltage must occur in the form of voltage drop in this resistance until the breaking current is reached. Therefore, it is necessary to realise a sufficiently small earthing resistance (see formula 9.1.)
UB perm |
maximum permissible contact voltage (e.g. 65 V) |
Ia |
breaking current |
RS |
earthing resistance |
Fig. 9.5. shows an example of a fault-current circuit
Fig. 9.5. Fault circuit involved in
the protective measure called protective earthing
IF - fault current
RS - earthing resistance
RB - operational earthing resistance
Depending on the fuse used, the breaking current must be selected in such a way that it is higher by the factor k than the rated current of the fuse (formula 9.2.)
Ia = k In
where:
Ia |
breaking current |
k |
switching off factor |
In |
rated current of the fuse |
In this way it is to be achieved that, in case of a fault, the circuit is interrupted within a adequately short time. High values of k ensure an increased safety due to a quicker response of the fuse but in many cases they cannot be realised by an economically justifiable expense. The minimum values of k are specified, in special regulations in dependence of the type of fuse connected.
For the return flow of the fault current, the water pipes may be used if permission is given. But this is rarely used today because no-metallic water pipes are increasingly employed.