8.4. Power of Three-phase Current
For calculating the power of three-phase systems, the same
relations are applicable as for the calculation of the power of alternating
current systems. In accordance with the phase angle involved, a distinction is
also made between effective power, reactive power and apparent power.
The star connection of three equal resistors is shown in Fig.
8.13.
For the total power, we have
P = 3 ·
UStr · IL · cos j
When the power is to be determined, on the basis of the
line-to-line voltage UL, the following holds when using equation u.2.


(8.4.)

Fig. 8.13. Star connection of three
resistors
When three equal resistors are connected in delta (Fig. 8.14.),
the total power is written as
P = 3 ·
UL · IStr · cos j

Fig. 8.14. Delta connection of three
resistors
When the line-to-line current is used, the following holds when
using equation 8.3.


(8.5.)
where:
UL |
line-to-line voltage |
IL |
line-to-line current |
cos j |
power factor |
A comparison of the equations 8.4. and 8.5. shows that,
independent of the given type of connection, the same equations for calculating
the power are given.
When the phase load is unequal, the total power is obtained in
the form of the sum of the powers in the three phases to be determined
individually.
Example 8.3.
Three resistors of 800 W each
have to be interposed in a three-phase network of 380 V one time in star
connection and another time in delta connection. Calculate the effective power
involved in each case.
Given:
UL = 380 V
R = 800 W
cos j =
1
To be found:
effective power P for star connection and for delta
connection
Solution:
star connection of the three
resistors

In star connection, only the phase voltage drops at the three
resistors. Hence, for the current IL we have

This expression is entered in the initial equation
P = (380 V)2/800 W
P = 180.5 W
delta connection of the three resistors
P = 3 · UL · IStr · cos
j
Since the full line-to-line voltage is applied to each resistor,
we have for the phase current
IStr = UL/R
This expression is entered in the initial equation
P = 3 ·
UL2/R · cos j
P = 3 · (380
V)2/800 W
P = 541.5
W
At the three resistors, a total power of 180.5 W is obtained, in
star connection and of 541.5 W in delta connection.
In practice frequently advantage is taken of the possibility of
obtaining different powers by changing the type of connection of the various
loads. For example, for three-phase motors, there are special switching devices
which enable the changing over from star connection to delta connection and vice
versa.
The power of a three-phase system can be determined
from the sum of the individual powers in the three phases in ease of unequal
phase loads or from the relation given in equation 8.4. in case of equal loads
irrespective of the type of connection.
Questions and problems:
1. Determine the effective power of three resistors
in star connection of 200 W if the latter are
connected to a three-phase network with a line-to-line voltage of 220 V!
2. Determine the effective power when the three resistors of
problem 1. are in delta connection!
3. Three unequal effective resistances (80 W, 200 W, 500 W) have to be connected in star and in delta arrangement
to a three-phase network with a line-to-line voltage of 380 V. Determine the
total effective
power!